Analysis of axial magnetic field in vacuum interrupters with cup type axial magnetic field contacts
发布时间:2025-04-30
点击次数:
- 发布时间:
- 2025-04-30
- 论文名称:
- Analysis of axial magnetic field in vacuum interrupters with cup type axial magnetic field contacts
- 发表刊物:
- 15th COMPUMAG
- 摘要:
- Effects of 7 contact design parameters on magnetic field characteristics of vacuum interrupters with cup type axial magnetic field contacts are studied by using 3D finite element method. The results show that: (1) Axial magnetic flux density weakens with increasing contact diameter or contact gap. Increasing sweep angle of coil segments or quantities of coil segments can strengthen it. Other design parameters such as slope angle of coil segments, contact plate slots quantities and contact material using CuCr50 or CuCr25 have little influence on it. (2) Phase shifttime changes little when design parameters vary in a wide range. (3) Maximum current density in cup or contact plates becomes smaller by increasing contact diameter or contact plate slots quantities, decreasing sweep angleof coil segments, choosing an appropriateslope angle of coil segments or a properquantity of coil segments, or using CuCr50 contact material. (4) Conductor resistance of contacts decreases with increasing contact diameter or slope a
Technology Research Database
- 合写作者:
- Zhang, Xuan; Liu, Zhi Yuan; Wang, Zhong Yi
- 卷号:
- 2005,VOL 4
- 页面范围:
- 92-93
- 是否译文:
- 否
- 发表时间:
- 2005-08-24