Papers

A New Slot Type Axial Magnetic Field Contact with Low Resistance

Release Time:2025-04-30
Hits:
Date:
2025-04-30
Title of Paper:
A New Slot Type Axial Magnetic Field Contact with Low Resistance
Journal:
ISDEIV 2006
Summary:
This paper introduces a new slot type axial magnetic field (AMF) contact. It has lower resistance compared with its counterpart conventional one by introducing a contactbridgethat substitutes for stainless steel support in conventional contact. There is a gap between the contact bridge and contact plate. In close position, the contactbridge is pressed on contactplate by contact force and coil deformation. So current goes throughthecontact bridgeto reachcontactplate directly.Inaninterruptionoperation,thegaprestoreswithcontact force disappearing, whichpushes currentpassingthrough
coils ofthe slot typeAMFcontact. So sameAMFcan be generated as a conventional one. Asa result, short circuit
current interruption tests showed that the interrupting capacity ofthe vacuuminterrupterwith newcontactswas notlessthanthatwithconventional contacts.Resistance of vacuum interrupterwith conventional contactis 10-12pQ
at contact force2000N.It decreasedto 7pQwith the new contact.
Co-author:
Zhiyuan Liu, Zheng Wang, Jimei Wang
Volume:
vol.x no.x
Page Number:
293-296
Translation or Not:
No
Date of Publication:
2006-10-13